Home ProductsAdjustable Load Bank

Yellow Tturbines Automatic Load Bank Parallel Testing With Communication Pattern

Good quality Portable Load Bank for sales
Good quality Portable Load Bank for sales
We are highly appreciating the neat finishing and will organized system. To be honest with you,as I am in power generation since more than 30 years, your load bank is the best I ever see.It is perfect. Thank you and thank everybody who participated in design manufacturind packaging and handling these banks.

—— Ghalib Zayed

Pls contact Mr.Dong Thai topromote and sell your loadbank. I told Mr.Dong Thai that we are happy with KX Loadbank and also happy with your services

—— Tuong

I'm Online Chat Now

Yellow Tturbines Automatic Load Bank Parallel Testing With Communication Pattern

China Yellow Tturbines Automatic Load Bank Parallel Testing With Communication Pattern supplier
Yellow Tturbines Automatic Load Bank Parallel Testing With Communication Pattern supplier Yellow Tturbines Automatic Load Bank Parallel Testing With Communication Pattern supplier

Large Image :  Yellow Tturbines Automatic Load Bank Parallel Testing With Communication Pattern

Product Details:

Place of Origin: China
Brand Name: Kaixiang
Certification: ISO9001
Model Number: AC415V-500kW

Payment & Shipping Terms:

Minimum Order Quantity: 1 set
Price: negotiable
Packaging Details: Packaged in wooden cases
Delivery Time: Within 35 working days
Payment Terms: L/C, T/T, Western Union
Supply Ability: 32 Sets / Month
Contact Now
Detailed Product Description
Model: AC415V-500kW Rated Power: 500 KW
Casing Color: As Required Rated Voltage: AC415V
Frequency: 50 HZ Display Precision: 0.5 Class

AC415V-500kW Adjustable Load Bank With Frequency 50 HZ And Best Sales
Introduction

AC415V-500kW Automatic Load Bank can accurately test output power and load capacity with all kinds of generators, generator sets for all main electrical parameters including the dynamic parameters tested.

Application

1. Periodic excercising of stand-by engine generator sets

2. Ups system testing
3. Load optimization in prime power applications
4. Factory testing of turbines
5. factory testing of engine generator sets
6. To reducewet stacking problems

 

Technical specification

Technical Parameters
Rating Voltage/Frequency AC 415V/50Hz, 3 phase 4 wire
Max Load Power Resistive Load: 500kW
Load Step Resistive Load.11 steps; 1kW,2 kW,2 kW,5 kW,10 kW,10 kW,20 kW, 50kW,100 kW,100 kW,200 kW.
Power Factor 1
Load Tolerance(each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Control Power Supply input 380VAC 3 phase 4 wire 50hz, phase voltage 220VAC.
Wire Connection

Load Power Supply Input——Copper bar (star connection)

Control power supply input——Connector bar

Communication Interface RS232
Insulation Class F
Working Mode Continuous Working
Cooling Forced air cooling,Horizontal inlet air,Horizontal outlet
Transportation Hoisting, there are lifting lug in top of case and wheel castors in bottom
Chassis color gray(RAL7035)
Size

Approximately; 1460*1980*1800

(Width *Length *Height)

Weight Approximately;750kg
Operating Environment Parameter
Ambient Temperature -10℃~+50℃
Relative Humidity ≤95%
Altitude ≤2500 meters
Atmospheric Pressure 86~106kPa
 
Main features

--Communication pattern: Intelligent control use photoelectric isolated RS485 interface connect to PC, with great anti-interference performance to make system control stable. Also user can use USB or RS232 through converter.

--Load pattern: Manual Load or Automatic Load.

--Manual Load: Input power, system will load according to preset power.

--Automatic load: user can preset power and length of working time of several load periods, as per 0%→25%→50%→75%→100% or 110% to make testing.

--Parallel testing: when several load bank work in parallel, use can make parallel testing via software, can display, record parameters of every load bank and whole system parameter of parallel operation.

--Real-time parameter: through software to display voltage, current, power, power factor, frequency and time, etc.

--Security monitoring and control: monitor working state of the load bank by watching software light, when abnormally stop and protect, it can show the reason.

--Data collection interval: the minimum data storage interval is two seconds.

--Data save and query: all the test data is saved in the software, easy to query in the history testing data.