Home ProductsElectrical Load Bank

Intelligent 500Kw Variable Load Bank 380VAC/50Hz 3 Phase 4 Wire

Good quality Portable Load Bank for sales
Good quality Portable Load Bank for sales
We are highly appreciating the neat finishing and will organized system. To be honest with you,as I am in power generation since more than 30 years, your load bank is the best I ever see.It is perfect. Thank you and thank everybody who participated in design manufacturind packaging and handling these banks.

—— Ghalib Zayed

Pls contact Mr.Dong Thai topromote and sell your loadbank. I told Mr.Dong Thai that we are happy with KX Loadbank and also happy with your services

—— Tuong

I'm Online Chat Now

Intelligent 500Kw Variable Load Bank 380VAC/50Hz 3 Phase 4 Wire

China Intelligent 500Kw Variable Load Bank 380VAC/50Hz 3 Phase 4 Wire supplier
Intelligent 500Kw Variable Load Bank 380VAC/50Hz 3 Phase 4 Wire supplier Intelligent 500Kw Variable Load Bank 380VAC/50Hz 3 Phase 4 Wire supplier

Large Image :  Intelligent 500Kw Variable Load Bank 380VAC/50Hz 3 Phase 4 Wire

Product Details:

Place of Origin: HEBEI CHINA
Brand Name: KAIXIANG
Certification: ISO9001
Model Number: AC400-500KW

Payment & Shipping Terms:

Minimum Order Quantity: ONE SET
Price: negotiable
Packaging Details: WOODEN CASE
Delivery Time: ONE MONTH AFTER GET DEPOSIT
Payment Terms: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability: 20 SETS ONE MONTH
Contact Now
Detailed Product Description
Resistive Load: 500KW Load Tolerance: ±3%
Control Power: 380VAC/50Hz, 3 Phase 4 Line Insulation: F
Altitude: ≤1500 Meter Color: Grey

Intelligent 500Kw Dummy Electronic Load Bank Testing Equipment
 
Product Description 
 

1.  Automatic AC load bank main used to test the capability and aging degree for high-power ups on-line, inverter, switch power and diesel generator set for electric power, telecom department and manufacturer.

2.  It can ensure the reliability of constant power charge that adopts uniformly stepped power input, energy consumption work model and forced air-cooling model.

3. It is of high power density, no red hot phenomenon and automatic protection function overheated.

4. It can’t be overheated and broken when the fans stop working

5. The complete machine can be operated simply and maintain convenient that adopts module design. It can test voltage and current according to client’s request, and provide scientific test measures for high-power AC equipment.

 
Technical Parameter 

Rating Voltage/Frequency 400VAC/50Hz, 3 phase 4 wire,
Rated Load Power Resistive load: 500kW
Installed Capacity Resistive load: 500kW
Load Step 1,2,2,5,10,10,20,50,100,100,200kW
PF(Power Factor) 1
Load Tolerance (each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Control Power 380VAC/50Hz, 3 phase 4 wire,
Wire Connection

Load power supply input——Copper bar (star coupling)
Control power supply input——terminal block

Insulation F
Protection Grade IP21
Way of Working Continuous Working
Casing Dimensions and Cooling about 1550*1250*1680mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling
Weight About 750kgs/set
Transportation Hoisting, there are lifting lug in top of casing
Casing Color Grey(RAL7035)
Ambient Temperature -10℃~+50℃
Relative Humidity ≤95%
Altitude ≤1500 meter
Atmospheric Pressure 86~106kPa
Contactor Schneider
Fuse DELIXI
MCU INFINEON
Data processing software Kaixiang(self-developed)
Alloy Resistance Kaixiang(self-developed)

 
Product Advantage
 

Safety monitoring: User can know the working conditions of load bank through software indicating light. When in abnormal stop protection, software will indicate the reasons of stopping.

Data collection interval: the min saving interval is 2 seconds.

Data saving and in query: testing data could be saved in software, user can query at any time.

Data display: it could display real-time data and history data; user can print voltage, current, frequency, power graphs and charts.

Charts and graphs are output in format of JPG while testing data output in Excel format, and all can be printed.

 
Application

 

1.Manufacturers of small gas engines also use load banks to test newly manufactured engines under various mechanical loads.

2.This is accomplished by connecting the engine to the load bank via a device called a dynamometer.

3.engine performance is monitored and, if necessary, adjustments are made to ensure the product performs within intended specifications.

 